AISI S250-21 | “North American Standard for Thermal Transmittance of Building Envelopes With Cold-Formed Steel Framing, 2021 Edition”
https://www.steel.org/2021/09/aisi-publishes-aisi-s250-21-north-american-standard-for-thermal-transmittance-of-building-envelopes-with-cold-formed-steel-framing-2021-edition/
Thermal transmittance (U-factors) of above-grade wall assemblies constructed with standard Cshape studs and track,
where the framing spacing is 6, 12, 16 or 24 inches on-center, shall be determined in accordance with Equation
B3.1.8-1 using Sections B3.1.1 through B3.1.8 or shall be determined in accordance with Appendix 1. Where a
non-standard designation thickness for the cold-formed steel framing member is applicable, values for the OTZ coefficients
from Table B3.1.11 and thermal conductivity from Table B3.1.3-1 shall be based on linear interpolation for the
intermediate value of designation thickness or shall be based on the next larger standard designation thickness.
Extrapolation is not permitted.
NOTE: AISI does not provide an 'SI' version of the coefficients in Table B3.1.11. therefor
ALL values in this module are in imperial units. This includes R-Values, U-Values, and dimensions.
"""
from honeybee_ph_utils.enumerables import CustomEnum
[docs]
class StudSpacingInches(CustomEnum):
allowed = [
"6",
"12",
"16",
"24",
]
def __init__(self, _value=1):
# type: (str | int) -> None
super(StudSpacingInches, self).__init__(_value)
[docs]
class StudThicknessMil(CustomEnum):
allowed = [
"33",
"43",
"54",
"68",
]
def __init__(self, _value=1):
# type: (str | int) -> None
super(StudThicknessMil, self).__init__(_value)
# [AISI S250-21w/S1-22] Table B3.1.1-1 | OTZ Coefficients
OTZ_COEFFICIENTS = {
StudSpacingInches("6"): {
StudThicknessMil("33"): [1.8583, 0.07478, 0.1488, -0.001859, -0.005103, 0.002013],
StudThicknessMil("43"): [1.9826, 0.0736, 0.1501, -0.001816, -0.005314, 0.002149],
StudThicknessMil("54"): [2.0814, 0.07131, 0.1522, -0.001713, -0.005295, 0.00205],
StudThicknessMil("68"): [2.211, 0.06816, 0.1508, -0.001652, -0.005576, 0.0023],
},
StudSpacingInches("12"): {
StudThicknessMil("33"): [2.1584, 0.05118, 0.2079, -0.001384, -0.005367, 0.002253],
StudThicknessMil("43"): [2.2077, 0.06381, 0.1992, -0.001713, -0.006235, 0.003499],
StudThicknessMil("54"): [2.2974, 0.06439, 0.2043, -0.001686, -0.006908, 0.003943],
StudThicknessMil("68"): [2.4136, 0.05185, 0.2166, -0.001216, -0.00684, 0.003748],
},
StudSpacingInches("16"): {
StudThicknessMil("33"): [2.2771, 0.03843, 0.1964, -0.001141, -0.005237, 0.003197],
StudThicknessMil("43"): [2.3769, 0.04037, 0.2011, -0.001195, -0.005677, 0.003714],
StudThicknessMil("54"): [2.4945, 0.04089, 0.1996, -0.001161, -0.005719, 0.003927],
StudThicknessMil("68"): [2.5917, 0.04614, 0.1922, -0.001391, -0.005884, 0.004606],
},
StudSpacingInches("24"): {
StudThicknessMil("33"): [3.182, -0.02946, 0.2432, 0, -0.00752, 0.003572],
StudThicknessMil("43"): [2.751, 0.0128, 0.1965, -0.00074, -0.006709, 0.005169],
StudThicknessMil("54"): [2.572, 0.00426, 0.2285, 0, -0.0061, 0.003509],
StudThicknessMil("68"): [2.936, -0.00324, 0.2256, 0, -0.00643, 0.00419],
},
} # type: dict[StudSpacingInches, dict[StudThicknessMil, list[float]]]
# [AISI S250-21w/S1-22] Table B3.1.3-1 | Cold-Formed Steel Thermal Conductivity (Btu/hr-ft2-F)
STEEL_CONDUCTIVITY = {
StudThicknessMil("33"): 381.0,
StudThicknessMil("43"): 495.0,
StudThicknessMil("54"): 622.0,
StudThicknessMil("68"): 783.0,
}
[docs]
def overall_thermal_zone(
c_0,
c_1,
c_2,
c_3,
c_4,
c_5,
r_cavity,
r_ext_insulation,
):
# type: (float, float, float, float, float, float, float, float) -> float
"""
[AISI S250-21w/S1-22] B3.1.1 Overall Thermal Zone.
The overall thermal zone (OTZ) shall be determined in accordance with Equation B3.1.1-1.
The appropriate coefficients for use in Equation B3.1.1-1 shall be obtained from Table B3.1.11
with the given on-center spacing of framing members and C-shape designation thickness.
Eq. B3.1.1-1: OTZ = C_0 + C_1 * R_cav + C_2 * R_she + C_3 * R_cav^2 + C_4 * R_she^2 + C_5 * R_cav * R_she
r_cavity (r_cav) = R_air + R_ins
* R_ins: Thermal resistance (R-value) of cavity insulation (h-ft2-F/Btu)
* = 0 where wall cavity contains no insulation
* R_air: Thermal resistance (R-value) of the cavity air space (h-ft2-F/Btu)
* = 0.91 where wall cavity contains an air space
* = 0 where wall cavity contains no air space
Args:
C_0: Coefficient from Table B3.1.1-1
C_1: Coefficient from Table B3.1.1-1
C_2: Coefficient from Table B3.1.1-1
C_3: Coefficient from Table B3.1.1-1
C_4: Coefficient from Table B3.1.1-1
C-5: Coefficient from Table B3.1.1-1
r_cavity (R_cav): Total thermal resistance (R-value) of the wall cavity (h-ft2-F/Btu)
r_ext_insulation (R_she): Thermal resistance (R-value) of exterior continuous insulation (hr-ft2-F/Btu). R_she does
not include wood or gypsum panels.
Returns:
OTZ: Overall thermal zone (inch)
"""
return (
c_0
+ c_1 * r_cavity
+ c_2 * r_ext_insulation
+ c_3 * r_cavity**2
+ c_4 * r_ext_insulation**2
+ c_5 * r_cavity * r_ext_insulation
)
[docs]
def framing_factor(stud_flange_width_inch, stud_thickness_mils):
# type: (float, float) -> float
"""
[AISI S250-21w/S1-22] B3.1.2 C-Shape Framing Factor.
The C-shape framing factor (FFcs) for the cold-formed steel framing shall be determined in
accordance with Equation B3.1.2-1:
Eq. B3.1.2-1: FF_cs = (CFS_t / 1000) / CFS_flange
Args:
stud_thickness_mils (CFS_t): Designation thickness of cold-formed steel framing member (mils)
stud_flange_width_inch (CFS_flange): Flange width of cold-formed steel framing member (inches)
Returns:
float: (FF_cs) C-shape framing factor (unitless)
"""
return ((stud_thickness_mils) / 1000) / stud_flange_width_inch
[docs]
def stud_web_r_value(stud_depth_inch, conductivity):
# type: (float, float) -> float
"""
[AISI S250-21w/S1-22] B3.1.3.1 Thermal Resistance of C-Shape Web.
The thermal resistance (R-value) of the web of the cold-formed steel framing member (Rs- wall )
shall be determined in accordance with Equation B3.1.3-1:
* R_s-wall = CFS_depth / k
Args:
stud_depth (CFS_depth): Web depth of cold-formed steel framing member that is in contact with cavity insulation (inches)
as illustrated by Figure B3.1.3-1 without cavity air space and Figure B3.1.3-2 with cavity air space
conductivity (k): Thermal conductivity of cold-formed steel as selected from Table B3.1.3-1 (Btu/h-ft2-F)
Returns:
float: (R_s-wall) Thermal resistance (R-value) of the web of the cold-formed steel framing member (h-ft2-F/Btu)
"""
return stud_depth_inch / conductivity
[docs]
def u_value_at_stud(framing_factor, r_value_cavity_insulation, r_value_stud_web):
# type: (float, float, float) -> float
"""
[AISI S250-21w/S1-22] B3.1.3.2 Thermal Transmittance of Cavity with Insulation.
The parallel path thermal transmittance (U-factor) of the assembly where insulation(s) are in contact with
cold-formed steel framing member (U1 ) shall be determined in accordance with Equation B3.1.3-2. Where there is
no insulation in the wall cavity, Equation B3.1.3-2 shall not be used and the resultant value of R 1 in
Equation B3.1.3-3 shall be “zero” (0).
* U_1 = (1 - FFcs) / R_ins + FFcs / Rs-wall
Args:
framing_factor (FF_cs): C-shape framing factor determined from Equation B3.1.2-1
r_value_cavity_insulation (R_ins): Thermal resistance (R-value) of cavity insulation (h-ft2-F/Btu)
r_value_stud_web (R_s-wall): Thermal resistance (R-value) of the wall assembly at the web of the cold-formed steel framing
member determined from Equation B3.1.3-1 (h-ft2-F/Btu)
Returns:
float: (U_1) Parallel path thermal transmittance (U-factor) of the assembly where insulation(s) are
in contact with cold-formed steel framing member (Btu/hr-ft2-F)
"""
return (1 - framing_factor) / r_value_cavity_insulation + framing_factor / r_value_stud_web
[docs]
def r_value_series_stud_path(
r_ext_cladding,
r_ext_insulation,
r_ext_sheathing,
r_3,
r_int_sheathing,
r_se=0.17,
r_si=0.68,
):
# type: (float, float, float, float, float, float, float) -> float
"""
[AISI S250-21w/S1-22] B3.1.6.1 Thermal Resistance (R-value) of Series Paths | C-Shape Path.
The effective thermal resistance (R-value) of all materials in the design assembly in series for the
path containing cold-formed steel (R_sps), illustrated as the C-shape path in Figure B3.1.3-1 or
Figure B3.1.3-2, shall be determined using Equation B3.1.6-1:
* R_sps = R_o + Side_ext + R_she + Sheath_ext + R_3 + Sheath_int + R_i
Args:
r_ext_cladding (Side_ext): Thermal resistance (R-value) of exterior siding (h-ft2-F/Btu)
r_ext_insulation (R_she): Thermal resistance (R-value) of exterior continuous insulation (h-ft2-F/Btu)
r_ext_sheathing (Sheath_ext): Thermal resistance (R-value) of all exterior sheathing(s) (h-ft2-F/Btu)
R_3: Thermal resistance (R-value) determined from Equation B3.1.5-1 (h-ft2-F/Btu)
r_int_sheathing (Sheath_int): Thermal resistance (R-value) of all interior sheathing(s) (h-ft2-F/Btu)
r_se (R_o): [Default=0.17] Thermal resistance (R-value) of outside air film (h-ft2-F/Btu)
r_si (R_i): [Default=0.68] Thermal resistance (R-value) of inside air film (h-ft2-F/Btu)
Returns:
float: (R_sps) Effective thermal resistance (R-value) of all materials in the design assembly
in series for the path containing cold-formed steel (h-ft2-F/Btu)
"""
return r_se + r_ext_cladding + r_ext_insulation + r_ext_sheathing + r_3 + r_int_sheathing + r_si
[docs]
def r_value_series_cavity_path(
r_ext_cladding,
r_ext_insulation,
r_ext_sheathing,
r_cavity_insulation,
r_int_sheathing,
r_se=0.17,
r_si=0.68,
):
# type: (float, float, float, float, float, float, float) -> float
"""
[AISI S250-21w/S1-22] B3.1.6.1 Thermal Resistance (R-value) of Series Paths | Cavity Path.
B3.1.6.2 Cavity Path The thermal resistance (R-value) of all materials in the design assembly in series for the path
containing only cavity insulation (R_spc), illustrated as the cavity path in Figure B3.1.31 or Figure B3.1.3-2,
shall be determined using Equation B3.1.6-2:
* R_spc = R_o + Side_ext + R_she + Sheath_ext + R_ins + R_air + Sheath_int + R_i
Args:
R_o: Thermal resistance (R-value) of outside air film (h-ft2F/Btu)
r_ext_cladding (Side_ext): Thermal resistance (R-value) of exterior siding (h-ft2F/Btu)
r_ext_insulation (R_she): Thermal resistance (R-value) of exterior continuous insulation (h-ft2F/Btu)
r_ext_sheathing (Sheath_ext): Thermal resistance (R-value) of all exterior sheathing(s) (h-ft2F/Btu)
r_cavity_insulation (R_ins): Thermal resistance (R-value) of cavity insulation (h-ft2F/Btu)
R_air: Thermal resistance (R-value) of the cavity air space (h-ft2F/Btu)
: 0.91 where wall cavity contains an air space
: 0.00 where wall cavity contains no air space
r_int_sheathing (Sheath_int): Thermal resistance (R-value) of all interior sheathing(s) (h-ft2F/Btu)
R_i: Thermal resistance (R-value) of inside air film (h-ft2F/Btu)
Returns:
float: (R_spc) Effective thermal resistance (R-value) of all materials in the design assembly
in series for the path containing only cavity insulation (h-ft2-F/Btu)
"""
return r_se + r_ext_cladding + r_ext_insulation + r_ext_sheathing + r_cavity_insulation + r_int_sheathing + r_si
[docs]
def overall_thermal_zone_framing_factor(_overall_thermal_zone, _stud_spacing_inch):
# type: (float, float) -> float
"""
[AISI S250-21w/S1-22] B3.1.7 OTZ Framing Factor.
The OTZ Framing Factor (FF_otz) shall be determined using Equation B3.1.7-1:
* FF_otz = OTZ / FS
Args:
_overall_thermal_zone (OTZ): Overall thermal zone (inch)
_stud_spacing_inch (fs): Spacing of cold-formed steel framing members (inches)
Returns:
float: (FF_otz) OTZ Framing Factor (unitless)
"""
return _overall_thermal_zone / _stud_spacing_inch
[docs]
def u_value_total(_overall_thermal_zone_framing_factor, _r_value_series_cavity_path, _r_value_series_stud_path):
# type: (float, float, float) -> float
"""
[AISI S250-21w/S1-22] B3.1.8 Overall Thermal Transmittance (U-Factor).
The overall thermal transmittance (U-factor) of the above-grade wall assembly (U_o)
shall be determined using Equation B3.1.8-1:
* U_o = (1 - FF_otz) / R_spc + FF_otz / R_sps
Args:
_overall_thermal_zone_framing_factor (FF_otz) : OTZ Framing Factor determined from Equation B3.1.7-1 (dimensionless)
_r_value_series_cavity_path (R_spc) : Thermal resistance (R-value) of all materials in the design assembly
in series for the cavity path determined from Equation B3.1.6-2 (h-ft2-F/Btu)
_r_value_series_stud_path (R_sps) : Thermal resistance (R-value) of all materials in the design assembly
in series for the C-shape path determined from Equation B3.1.6-1 (h-ft2-F/Btu)
Returns:
float: (U_o) Overall thermal transmittance (U-factor) of the above-grade wall assembly (Btu/hr-ft2-F)
"""
return (
1 - _overall_thermal_zone_framing_factor
) / _r_value_series_cavity_path + _overall_thermal_zone_framing_factor / _r_value_series_stud_path
[docs]
def calculate_stud_cavity_effective_u_value(
_r_ext_cladding,
_r_ext_insulation,
_r_ext_sheathing,
_r_cavity_insulation,
_stud_spacing_inch,
_stud_thickness_mil,
_stud_flange_width_inch,
_stud_depth_inch,
_steel_conductivity,
_r_int_sheathing,
_r_se=0.17,
_r_si=0.68,
):
# type: (float, float, float, float, StudSpacingInches, StudThicknessMil, float, float, float, float, float, float) -> float
try:
C0, C1, C2, C3, C4, C5 = OTZ_COEFFICIENTS[_stud_spacing_inch][_stud_thickness_mil]
except KeyError as e:
msg = "The given stud spacing: '{}' and stud-thickness '{}' is not supported. ".format(
_stud_spacing_inch.value, _stud_thickness_mil.value
)
msg += "Please use one of the following combinations:\n"
msg += "\tStud Spacing: {}\n".format(", ".join(StudSpacingInches.allowed))
msg += "\tStud Thickness: {}\n".format(", ".join(StudThicknessMil.allowed))
msg += "Error: {}".format(e)
raise KeyError(msg)
otz = overall_thermal_zone(C0, C1, C2, C3, C4, C5, _r_cavity_insulation, _r_ext_insulation)
ff = framing_factor(_stud_flange_width_inch, float(_stud_thickness_mil.value))
web_r_value = stud_web_r_value(_stud_depth_inch, _steel_conductivity)
stud_u_value = u_value_at_stud(ff, _r_cavity_insulation, web_r_value)
r_1 = 1 / stud_u_value
r_2 = 0 # <----- TODO: Calculate this properly calc U_2
r_3 = r_1 + r_2
r_stud_path = r_value_series_stud_path(
_r_ext_cladding, _r_ext_insulation, _r_ext_sheathing, r_3, _r_int_sheathing, _r_se, _r_si
)
r_cavity_path = r_value_series_cavity_path(
_r_ext_cladding, _r_ext_insulation, _r_ext_sheathing, _r_cavity_insulation, _r_int_sheathing, _r_se, _r_si
)
otz_ff = overall_thermal_zone_framing_factor(otz, float(_stud_spacing_inch.value))
u_overall = u_value_total(otz_ff, r_cavity_path, r_stud_path)
r_overall = 1 / u_overall
# Get the stud cavity U-Value by itself
r_stud_cavity = (
r_overall - _r_ext_cladding - _r_ext_insulation - _r_ext_sheathing - _r_int_sheathing - _r_se - _r_si
)
u_stud_cavity = 1 / r_stud_cavity
return u_stud_cavity